RECOMMENDED FREQUENCIES OF FIXED WIRING PERIODIC INSPECTION AND TESTING
Electrical Installations


TYPE OF INSTALLATION ROUTINE CHECK MAXIMUM PERIOD BETWEEN INSPECTIONS AND TESTING
     
Domestic  
- -
Change of occupancy/10 years
Commercial  
1 year
Change of occupancy/5 years
Educational establishments  
4 months
5 years
Hospitals  
1 year
5 years
Industrial  
1 year
3 years
Residential accommodation  
at change of occupancy/1 year
5 years
Offices  
1 year
5 years
Shops  
1 year
5 years
Laboratories  
1 year
5 years
BUILDINGS OPEN TO THE PUBLIC      
Cinemas  
1 year
3 years
Church installations  
1 year
5 years
Leisure complexes excluding swimming pools  
1 year
3 years
Places of public entertainment  
1 year
3 years
Restaurants and hotels  
1 year
5 years
Theatres  
1 year
3 years
Public houses  
1 year
5 years
Village halls/Community centres  
1 year
5 years
SPECIAL INSTALLATIONS      
Agricultural & horticultural  
1 year
3 year
Caravans  
1 year
3 year
Caravan parks  
6 months
1 year
Highway power supplies  
as convenient
6 years
Marinas  
4 months
1 year
Fish farms  
4 months
1 year
Swimming pools  
4 months
1 year
Emergency lighting  
Daily/monthly
3 years
Fire alarms  
Daily/weekly/monthly
1 year
Launderettes  
1 year
1 year
Petrol filling stations  
1 year
1 year
Construction site installations  
3 months
3 months

Reference: Inspection and Testing Guidance Note 3; The IET, London, 2004 p 68